-40%
Top Quality ETCR4100 Double Clamp Digital Phase Meter ETCR-4100
$ 124.08
- Description
- Size Guide
Description
Introduction:
ETCR4100 pair of pliers digital phase table is my company has a well- developed specifically for field testing of various phases
of the instrument , with high accuracy, high stability, low power consumption, easy to use features . Can be measured directly in
the case of the circuit under test is not open between the two voltages , currents and phase voltages between the two currents
between , in addition, you can also determine the phase sequence of the three-phase transformer connection group , inductive,
capacitive circuits , test secondary loop and bus differential protection system , read travel protection CT phase relationship
between the groups , check the meter wiring is correct or not .
ETCR4100 double clamp digital phase meter with large LCD display with blue backlight , display clear, exquisite and
luxurious appearance.
ETCR4100 pair of pliers digital phase table for the power , petrochemical, metallurgy , railway , meteorology, industrial and
mining enterprises , scientific research institutions , metering sector.
Technical Specifications
:
1. Baseline conditions and working conditions
Affect the amount of
Baseline conditions
Working conditions
Remarks
Ambient temperature
23 1
-10 ~ 40
Environmental wet crossing
40% -60 %
< 85%
Signal waveform
Sine wave
Sine wave
= 0.05
Signal frequency
50HZ 1HZ
45HZ ~ 65HZ
Operating voltage meter
9V 0.1V
9V 1V
External electric field , magnetic field
Avoid
Measured wire position
Approximate geometric center of the test conductor position in jaws
2. General Specifications
Function
Various phases , phase sequence test ; transformer groups , inductive,
capacitive circuit discrimination
Power source
DC9V alkaline batteries (1.5V AA × 6)
Power consumption
Turn on the backlight most about 35mA, working about 40 hours of
continuous battery
Off the backlight , instrument consumes about 5mA, for about 300
hours of continuous battery
Display Mode
LCD display , blue backlight , suitable for dark places
LCD Size
70mm × 62mm
LCD display fields
64mm × 54mm
Meter size
Long generous : 196mm × 92mm × 54mm
Jaw size
7.5mm × 13mm
Sampling Rate
About 3 times / sec
Range
0 ~ 360
Accuracy
3
Resolution
1
Measuring the phase of the
signal amplitude range when
When measuring phase U1-U2 : 30V ~ 500V
When the measured phase I1-I2 : 10mA ~ 10.00A
Measured U1-I2 or I1-U2 phase when : 10V ~ 500V, 10mA ~ 10.00A
Data Retention
Press HOLD key to keep the test data , "DH" symbol is displayed
Automatic shutdown
About 15 minutes after startup , the meter automatically shut down to
reduce battery consumption
Voltage detection
When the battery voltage is lower than 7.8V ~ 8V, low battery symbol
appears , reminding replace batteries
Instrument Quality
Host about 550g ( with battery ) , table clamp about 170g × 2, test line
about 250g
Test line length
1.5m
Current Clamp Cable Length
2m
Working temperature and humidity
-10 ~ 40 ; 80% Rh or less
Storage Temperature and Humidity
-10 ~ 60 ; 70% Rh or less
Input impedance
Voltage circuit input impedance is : 2M
U1U2 measured phase voltage input impedance : 40K
Resistance to pressure
Between meter line and shell withstand sine wave AC voltage 1000V /
50Hz lasted one minute ; able to withstand voltage inputs between the
two sine wave AC voltage 500V / 50Hz trial lasted one minute
Insulation
The line between the meter and the shell , 10M between the two voltage inputs
Structure
Double insulation
Configuration Checklist
:
Meter
A Taiwan
Meter box
1
Current Clamp
2
Test line
4 ( red and black each 2 )
Battery
6 ( alkaline batteries : 1.5V AA)
Manual, warranty card, certificate
1 part
The standard package don't include batteries.Because,the international air shipping forbid to ship batteries,Hope you can understand .you can buy them in your local store or supermarket.